Smart Solar PV Inverters with Advanced Grid Support Functionalities
eBook - ePub

Smart Solar PV Inverters with Advanced Grid Support Functionalities

Rajiv K. Varma

Condividi libro
  1. English
  2. ePUB (disponibile sull'app)
  3. Disponibile su iOS e Android
eBook - ePub

Smart Solar PV Inverters with Advanced Grid Support Functionalities

Rajiv K. Varma

Dettagli del libro
Anteprima del libro
Indice dei contenuti
Citazioni

Informazioni sul libro

Learn the fundamentals of smart photovoltaic (PV) inverter technology with this insightful one-stop resource

Smart Solar PV Inverters with Advanced Grid Support Functionalities presents a comprehensive coverage of smart PV inverter technologies in alleviating grid integration challenges of solar PV systems and for additionally enhancing grid reliability. Accomplished author Rajiv Varma systematically integrates information from the wealth of knowledge on smart inverters available from EPRI, NREL, NERC, SIWG, EU-PVSEC, CIGRE, IEEE publications; and utility experiences worldwide. The book further presents a novel, author-developed and patented smart inverter technology for utilizing solar PV plants both in the night and day as a Flexible AC Transmission System (FACTS) Controller STATCOM, named PV-STATCOM. Replete with case studies, this book includes over 600 references and 280 illustrations.

Smart Solar PV Inverters with Advanced Grid Support Functionalities' features include:

  • Concepts of active and reactive power control; description of different smart inverter functions, and modeling of smart PV inverter systems
  • Distribution system applications of PV-STATCOM for dynamic voltage control, enhancing connectivity of solar PV and wind farms, and stabilization of critical motors
  • Transmission system applications of PV-STATCOM for improving power transfer capacity, power oscillation damping (POD), suppression of subsynchronous oscillations, mitigation of fault induced delayed voltage recovery (FIDVR), and fast frequency response (FFR) with POD
  • Hosting capacity for solar PV systems, its enhancement through effective settings of different smart inverter functions; and control coordination of smart PV inverters
  • Emerging smart inverter grid support functions and their pioneering field demonstrations worldwide, including Canada, USA, UK, Chile, China, and India.

Perfect for system planners and system operators, utility engineers, inverter manufacturers and solar farm developers, this book will prove to be an important resource for academics and graduate students involved in electrical power and renewable energy systems.

Domande frequenti

Come faccio ad annullare l'abbonamento?
È semplicissimo: basta accedere alla sezione Account nelle Impostazioni e cliccare su "Annulla abbonamento". Dopo la cancellazione, l'abbonamento rimarrà attivo per il periodo rimanente già pagato. Per maggiori informazioni, clicca qui
È possibile scaricare libri? Se sì, come?
Al momento è possibile scaricare tramite l'app tutti i nostri libri ePub mobile-friendly. Anche la maggior parte dei nostri PDF è scaricabile e stiamo lavorando per rendere disponibile quanto prima il download di tutti gli altri file. Per maggiori informazioni, clicca qui
Che differenza c'è tra i piani?
Entrambi i piani ti danno accesso illimitato alla libreria e a tutte le funzionalità di Perlego. Le uniche differenze sono il prezzo e il periodo di abbonamento: con il piano annuale risparmierai circa il 30% rispetto a 12 rate con quello mensile.
Cos'è Perlego?
Perlego è un servizio di abbonamento a testi accademici, che ti permette di accedere a un'intera libreria online a un prezzo inferiore rispetto a quello che pagheresti per acquistare un singolo libro al mese. Con oltre 1 milione di testi suddivisi in più di 1.000 categorie, troverai sicuramente ciò che fa per te! Per maggiori informazioni, clicca qui.
Perlego supporta la sintesi vocale?
Cerca l'icona Sintesi vocale nel prossimo libro che leggerai per verificare se è possibile riprodurre l'audio. Questo strumento permette di leggere il testo a voce alta, evidenziandolo man mano che la lettura procede. Puoi aumentare o diminuire la velocità della sintesi vocale, oppure sospendere la riproduzione. Per maggiori informazioni, clicca qui.
Smart Solar PV Inverters with Advanced Grid Support Functionalities è disponibile online in formato PDF/ePub?
Sì, puoi accedere a Smart Solar PV Inverters with Advanced Grid Support Functionalities di Rajiv K. Varma in formato PDF e/o ePub, così come ad altri libri molto apprezzati nelle sezioni relative a Physical Sciences e Energy. Scopri oltre 1 milione di libri disponibili nel nostro catalogo.

Informazioni

Anno
2021
ISBN
9781119214212
Edizione
1
Categoria
Energy

1
IMPACTS OF HIGH PENETRATION OF SOLAR PV SYSTEMS AND SMART INVERTER DEVELOPMENTS

Solar Photovoltaic (PV) power systems are being integrated at an unprecedented rate in both bulk power systems and distribution systems worldwide. It is expected that by 2050, solar PV systems will provide about 35% of global electricity generation [1]. Different countries, and their provinces and states, are setting up ambitious targets for PV system installations up to 100% renewables with substantial share of solar PV systems. Several grid impact studies with 100% Inverter Based Resources (IBRs) and Distributed Energy Resources (DERs) with a major component of solar PV systems have already been performed [2, 3]. While these systems significantly help in reducing overall greenhouse gas emissions, they present unique integration challenges which need to be understood and mitigated to derive full benefits from their applications. The solar PV systems are based on inverters. Power electronics technology provides new “smart” capabilities to the inverters in addition to their primary function of active power generation. These capabilities not only help solar PV systems mitigate different adverse impacts of their integration but also provide several valuable grid support functions.
This chapter presents the concepts of reactive power and active power control, which form the basis of smart inverter operation. The impact of such controls on system voltage and frequency is explained. The different challenges of integrating solar PV systems on a large scale in transmission and distribution systems are briefly described [4]. The evolution of smart inverter technology is then presented.

1.1 Concepts of Reactive and Active Power Control

1.1.1 Reactive Power Control

1.1.1.1 Voltage Control

Injection of reactive power at a bus causes the voltage to rise whereas absorption of reactive power causes the bus voltage to decline. Figure 1.1 illustrates a simple power system having an equivalent voltage E and equivalent network short circuit impedance with reactance X and resistance R. An inductor XL is connected as load at a bus termed Point of Common Coupling (PCC) to show the effect of reactive power absorption. The PCC voltage and inductor current are denoted by V and I, respectively. The impact of reactive power absorption by the inductor on the PCC voltage is examined through phasor diagrams for three cases of network impedance. The phasor diagrams for cases (a) R = 0 (purely inductive network), (b) X/R = 3 (substantially reactive network), and (c) X/R = 1/3 (substantially resistive network) are depicted in Figure 1.2a–c, respectively. The phasor diagrams are drawn with the phasor V as reference, which has same magnitude in all the three cases. The phasor diagrams can also be drawn with equivalent voltage E as reference phasor having the same magnitude, although the conclusions will be the same in both cases.
Schematic illustration of a simple power system with an inductor connected at PCC.
Figure 1.1 A simple power system with an inductor connected at PCC.
Schematic illustration of phasor diagrams for network with inductive load; (a) network with R Equals 0; (b) network with X/R Equals 3; (c) network with X/R Equals 1/3.
Figure 1.2 Phasor diagrams for network with inductive load; (a) network with R = 0; (b) network with X/R = 3; (c) network with X/R = 1/3.
In the absence of inductor XL, the PCC voltage is E. The lagging inductor current causes a voltage drop IR + jIX across the network impedance, thereby reducing the PCC voltage to V. Stated alternately, the reactive power absorption by the inductor reduces PCC voltage by an amount |E| − |V |.
For case (a) R = 0, it is evident from Figure 1.2a that the change in voltage is directly proportional to network reactance and the magnitude of inductive current I (which in turn is dependent on the size of the bus inductor XL). Hence for same inductive current, the larger the network reactance, larger is the change in bus voltage. This also implies that higher reactive power absorption (corresponding to higher I) will cause a larger reduction in voltage in weak systems.
The impact of system X/R ratio is seen from Figure 1.2b corresponding to X/R = 3, and from Figure 1.2c relating to X/R = 1/3. The same amount of reactive current and reactive power absorption in inductor XL causes a larger voltage drop in the network with higher X/R ratio.
Schematic illustration of a simple power system with a capacitor connected at PCC.
Figure 1.3 A simple power system with a capacitor connected at PCC.
Consider a capacitor XC being connected as load at the PCC as depicted in Figure 1.3. The impact of reactive power injection by the capacitor on the PCC voltage is investigated through phasor diagrams for three cases of network impedance. The phasor diagrams for cases (i) R = 0 (purely inductive network), (ii) X/R = 3 (substantially reactive network), and (iii) X/R = 1/3 (substantially resistive network) are displayed in Figure 1.4a–c, respectively. In the absence of capacitor, the PCC voltage is E. The leading capacitor current causes a voltage drop IR + jIX across the impedance of the network, thereby increasing the PCC voltage to V. Stated alternately, the reactive power injection by capacitor increases the PCC voltage by an amount |V | − |E|.
The change in voltage due to capacitive load is thus directly proportional to network reactance and the magnitude of capacitive current I (which in turn is dependent on the size of the bus capacitor XC), as seen from Figure 1.4a. Hence for same capacitive current, the larger the network reactance, higher is the change in voltage. This also demonstrates that higher reactive power injection (corresponding to higher I) will cause a larger increase in voltage in weak systems.
The impact of system X/R ratio is observed from Figure 1.4b corresponding to X/R = 3, and from Figure 1.4c ...